欧美性猛交xxxx乱大交蜜桃-国产青青草视频在线观看-伊人五月天婷婷成人-亚洲国产精品自拍在线观看-国产人妻久久精品一区二区三区-精品av传媒在线观看蜜桃-丰满人妻熟妇乱又伦精品视频三-亚洲综合一区二区精品久久-中文字幕三级人妻无码视频

Comprehensive Status Smart Sensor
WS-CJF-DACSW-112
WS-CJF-DACSW-112 comprehensive status smart sensor detects environmental temperature and humidity, UHF radio wave signals, transient ground voltage pulse signals, ultrasonic vibration frequency signals, etc. to monitor partial discharge defects and temperature and humidity changes inside the switch cabinet. At the same time, it can detect surface discharge, corona discharge, tip discharge, and insulator surface and internal discharge, and comprehensively locate the partial discharge power source.
Main functions and characteristics

1) The sensor structure is highly integrated, small in size, and simple in appearance;

2) Real-time online monitoring, strong anti-interference ability;

3) No maintenance required, operating time can reach 10 years;

4) Support PRPD/PRPS spectrum.

Technical parameter
  • 1. Shell
    Protection level : IP33
  • 2. Power supply
    1) Power supply : DC5V~36V
    2) Power consumption : ≤1W
  • 3. Communication
    1) Communication method : LoRa/RS-485
    2) Communication protocol : Meets the "Internet of Things Micropower Wireless Network Communication Protocol for Power Transmission and Transformation Equipment" , "Internet of Things Sensor Data Specification for Power Transmission and Transformation Equipment ", and Modbus protocol
    3) Reporting cycle : The reporting period is configurable, the default is 15 minutes
  • 4. Installation method
    Strong magnetic adsorption
  • 5. Data collection
    50Hz/100Hz correlation, peak value, average value, alarm value, discharge frequency, partial discharge type
  • 6. Measurement
    1) TEV detection bandwidth : 3~100MHz
    2) TEV detection dynamic range : 0~60dBmV
    3) Ultrasonic detection frequency band : 40±1kHz
    4) Ultrasonic detection dynamic range : -10~60dBuV
    5) Data map : PRPS, cumulative PRPD
    6) Power frequency synchronization : Internal sync/wireless sync
    7) Sampling frequency : Support adjustable
    8) Temperature measurement range : -40C~150℃
    9) Temperature measurement accuracy : ±1℃
    10) Humidity measurement range : ≤95%RH
    11) Humidity measurement accuracy : ±2%RH
  • 7. Working environment
    1) Operating temperature : -40℃~85'℃
    2) Operating humidity : ≤95%RH
    3) Atmospheric pressure : 86kPa~ 106.0kPa
Size Description

110mmx130mmx80mm